What is the difference between the C-type and the D-type of the miniature circuit breaker?
Take DZ47-63 circuit breaker as an example, C, D-type structure is the difference: electromagnetic discharge is not the same.
What is the demon? It is responsible for short circuit protection, simply means that:
B type: 3 times the rated current does not trip, 5 times the rated current trip, tripping time is less than or equal to 0.1 seconds;
--- for the protection of electronic current smaller load.
C type: 5 times the rated current does not trip, 10 times the rated current trip, tripping time is less than or equal to 0.1 seconds;
--- for the protection of conventional load and lighting lines. (Home)
D type: 10 times the rated current does not trip, 20 times the rated current trip, tripping time is less than or equal to 0.1 seconds;
--- For the protection of the starting current of the larger load, like the motor and the like.
How to determine the peak current when the load and short circuit generated current?
It is necessary to talk about the internal work structure.
Short circuit protection: When the short circuit fault occurs, the electromagnetic force of the electromagnetic coil to drive the coil inside the core to push the putter, putting the top of the lock, making the mechanism reset, to achieve breaking function.
The circuit breaker also has a function of overload protection: when the line overload fault occurs, the overload current causes the hot bimetallic element to bend and push the latch, making the mechanism reset, thus realizing the function of the breaking circuit breaker.
What is the difference between the C-type and the D-type of the miniature circuit breaker?
পাবলিশার্স : TAIXIতারিখ : 2017-07-11দেখেছে : 306
আরও পড়ুন
- Communications industry: optical communications maintain a high level of prosperity
- How should consumers choose small circuit breakers?
- Structural characteristics of load isolation switch
- How to ensure the quality of the electric meter box industry
- What is the difference between disconnectors and isolation switches?
- Isolation requirements for electrical isolation switch
- Working principle of DC circuit breaker
- Development of molded case circuit breakers
- Maintenance and inspection of AC contactor
- Attention should be paid to the installation, application and maintenance of molded case circuit breakers
- How does the overvoltage and undervoltage protection devices work?
- Installation of load isolation switch
- How to deal with abnormal AC contactor
- The comprehensive analysis of benefits of transparent meter box structure materials
- The future development trend of distribution box and distribution cabinet industry